Steam in a plant doesn’t just go from the boiler to the machine. It’s generated in the boiler house, sent through steam mains, reduced to the right pressure near the consumer, used in heat exchangers and process equipment, and finally returns as condensate. Each of these stages has its own typical problems. Pressure that’s too high for the equipment. Air that slows down start-up. Condensate that stays where it shouldn’t and causes water hammer. Energy use that nobody can see.
So a working steam system needs equipment for quite different tasks:
- safety, so pressure never exceeds what the system can handle;
- pressure and temperature control at the point of use;
- condensate removal from lines and equipment;
- air venting at start-up;
- measurement of steam consumption;
- boiler control in the boiler house.
Spirax Sarco makes components for each of these. Below, we follow the steam through a typical plant and look at which product group does which job. Steam traps are covered in detail in our separate articles, so here they get only a short mention.
What Spirax Sarco Offers for Steam Systems
The Spirax Sarco range on ELTRA TRADE is divided into these main groups:
- Valves: pressure reducing valves, control valves, safety valves, stop valves, actuators, and positioners;
- Steam traps: remove condensate from steam lines and equipment;
- Air vents and check valves: let air out and stop backflow;
- Flow meters: measure steam consumption;
- Boiler controls and systems: help the boiler house run safely and efficiently;
- Other products: accessories and related equipment.
The full Spirax Sarco product range is available in the ELTRA TRADE catalog.

AIO Snippet:
Spirax Sarco offers equipment for every stage of an industrial steam system: boiler controls and safety valves in the boiler house, stop valves, air vents, and check valves in distribution, pressure reducing and control valves at the point of use, steam traps for condensate removal, and flow meters for monitoring steam consumption.
The Boiler House: Control and Safety
Everything starts at the boiler. Two things matter most here: keeping the boiler running within its limits, and making sure pressure can never rise to a dangerous level.
Boiler controls look after things like water level and water quality. If dissolved solids in the boiler water build up too far, the boiler can foam and carry water over into the steam. If the water level drops, the boiler can be damaged. Control systems monitor these values and act automatically, for example by controlling blowdown.
Safety valves are the last line of protection. If all controls fail and pressure keeps rising, the safety valve opens and releases steam before the boiler or the downstream equipment is overloaded. Spirax Sarco safety valves such as the SV60 and SV615 series are listed in the catalog.
One rule is often misunderstood. A safety valve must be sized for the full relieving capacity, meaning the maximum amount of steam that could flow if a control valve fails wide open, not for the pipe it’s connected to. A valve chosen by pipe size alone may open on time but still be unable to release enough steam.
Steam Distribution: Stop Valves, Air Vents and Check Valves
From the boiler house, steam travels through the mains to different parts of the plant. This part of the system rarely gets much attention until something goes wrong.
Stop valves isolate sections of the system for maintenance. The catalog lists bellows-sealed stop valves, such as the BSA and A3S series. The bellows seal around the valve stem prevents the slow steam leaks that are typical of conventional gland packing.
Air vents remove air from the system. When a cold steam main is started up, it’s full of air, and air is a poor heat conductor. Even a thin layer of air on a heat transfer surface slows heating noticeably. Automatic air vents at the ends of steam mains and on larger equipment let the air out, so the system comes up to temperature faster.
Check valves stop condensate or steam from flowing back where it shouldn’t, for example into a condensate line from a higher-pressure header.
Steam mains also need steam traps at low points and at regular intervals to drain condensate that forms as the steam cools on its way. A common guideline is a drain point every 30–50 m on long, straight runs, plus one at every low point and before any rising section.
Pressure Reduction at the Point of Use
Boilers usually generate steam at a higher pressure than most process equipment needs. That’s intentional. Steam at higher pressure has a smaller volume, so it can be distributed through smaller pipes. The pressure is then reduced close to the consumer.
There’s a second benefit. Lower-pressure steam carries more latent heat per kilogram. At about 1 bar g, each kilogram releases roughly 2,200 kJ when it condenses. At 10 bar g it’s closer to 2,000 kJ. Reducing pressure before a heat exchanger therefore makes better use of the steam and protects equipment that isn’t rated for full boiler pressure.
The Spirax Sarco catalog includes several types of pressure reducing valves:
- Direct-acting pressure reducing valves, such as the SRV2S for steam and gases. They are simple and compact, and suit smaller and fairly steady loads.
- Pilot-operated pressure reducing valves, such as the DP series. They hold the downstream pressure more accurately when the load changes, which matters on larger or variable consumers.
- Sanitary pressure regulating valves, such as the SRV66 in 316L stainless steel, for clean steam in food and pharmaceutical applications.
A pressure reducing valve rarely works alone. A typical reducing station also includes isolation valves on both sides, a strainer to keep dirt out of the valve, a separator or drain to remove condensate ahead of it, pressure gauges, and, where the downstream equipment can’t take full upstream pressure, a safety valve after the reducing valve. Each of these parts protects either the valve or the equipment behind it.
Expert note: Size a pressure reducing valve for the actual steam flow, not the pipe size. An oversized valve spends most of its time almost closed, working right at its seat. Control becomes unstable and the seat wears faster.
Temperature and Process Control
Once the steam is at the right pressure, it has to be dosed to the process. That’s the job of control valves.
The catalog lists Spira-trol two-port control valves (LE33 and LEA33) and modulating valves (KE71 and KE73). They regulate the steam flow to heat exchangers, tanks, and process equipment to keep a product at the right temperature.
A control valve needs something to move it:
- Electric actuators, such as the AEL5;
- Pneumatic actuators, where compressed air is available;
- Positioners, such as the SP400, SP500, and EP500 series, which make sure the valve reaches the position the controller asks for.
For simpler tasks, there’s another option: self-acting temperature control. Systems such as the SA121 use a temperature sensor filled with fluid that expands with heat and moves the valve directly. They need no electricity and no compressed air.
When to choose which? Self-acting control works well for straightforward heating jobs, like a hot water tank or a simple heater, where steady temperature is enough and no remote control is needed. Electric or pneumatic actuation is the better choice when the temperature setpoint changes, the process has to be integrated into a control system, or the response has to be fast and precise.
Condensate Removal and Return
Once steam has given up its heat, it turns into condensate. This has to leave the equipment straight away.
Steam traps remove condensate while holding back live steam. If condensate stays in a heat exchanger, it covers part of the heating surface and reduces output. If it collects in steam lines, it can be picked up by fast-moving steam and slammed into bends and valves. That’s water hammer, and it can damage pipework and equipment.
The condensate itself is still valuable. It’s hot, clean, and already treated water. Returning it to the boiler house saves fresh water, water treatment chemicals, and the energy needed to heat cold make-up water.
There’s one more source of energy here that’s easy to overlook. When hot, high-pressure condensate is released to a lower pressure, part of it re-evaporates as flash steam. Instead of venting it to the atmosphere, many plants recover it and use it for low-pressure heating, such as preheating water or warming tanks.
Steam Flow Measurement
Many plants know how much fuel the boiler burns, but not where the steam actually goes. Steam flow meters fill that gap.
Metering steam by area or by machine helps to:
- see which processes use the most energy;
- allocate energy costs to departments or products;
- spot unusual consumption that may point to leaks or failed traps;
- check whether energy-saving measures actually work.
The ELTRA TRADE catalog includes Spirax Sarco flow meters. As with any steam meter, accuracy depends on correct sizing for the real flow range and on proper installation.
Where These Solutions Are Used
Food and beverage. Cooking, pasteurization, and CIP all need steam at controlled temperatures. Where steam touches the product, sanitary valves and clean steam are used.
Chemical and pharmaceutical. Reactor jackets need precise temperature control. Clean steam is used for sterilization.
Textiles and laundries. Dryers, ironing presses, and washing machines run on steam, often with many consumers on one system, each needing its own pressure.
Hospitals. Steam is used for sterilization and heating. Sterilizers need dry saturated steam, so separators and good drainage before them matter as much as the steam itself.
Paper and packaging. Drying cylinders use large amounts of steam, and condensate removal from them is especially demanding.
District and building heating. Steam heats water for buildings through heat exchangers.
How to Choose the Right Spirax Sarco Components
Before choosing any component, collect the steam data:
- Steam conditions: pressure, temperature, saturated or superheated.
- Flow rate at minimum, normal, and maximum load.
- Required downstream pressure or temperature.
- Control method: self-acting, pneumatic, or electric.
- Body material and pressure rating: cast iron, SG iron, steel, or stainless steel.
- Connection type: screwed, flanged, or sanitary.
- Clean steam or hygienic requirements.
- Safety valve set pressure and required relieving capacity.
- Space for installation and maintenance access.
| System stage | Task | Spirax Sarco product group |
| Boiler house | Safe and efficient boiler operation | Boiler controls, safety valves |
| Distribution | Isolation, air removal, backflow prevention | Stop valves, air vents, check valves |
| Point of use | Correct pressure | Pressure reducing valves, safety valves |
| Process | Correct temperature | Control valves, actuators, positioners, self-acting controls |
| After the process | Condensate removal and return | Steam traps |
| Whole system | Energy monitoring | Flow meters |
Common Mistakes in Industrial Steam Systems
- Sizing valves by pipe size: control is unstable and seats wear quickly.
- No safety valve after a pressure reducing valve, where one is required: if the reducing valve fails, downstream equipment sees full boiler pressure.
- No air vents at the ends of steam mains: start-up takes longer, and heating is slower.
- Poor drainage before control valves: condensate causes water hammer and erodes the valve seat.
- Standard valves in clean steam applications: materials and design don’t meet hygiene requirements.
- Oversized control valves: they work almost closed and hunt around the setpoint.
- No steam metering: losses and failed traps go unnoticed.
Expert Insight:
“Look at a steam system stage by stage: generation, distribution, pressure reduction, process use, and condensate return. At each point, define the task (safety, pressure, temperature, drainage, or measurement), then choose the Spirax Sarco component sized for the actual steam conditions and flow, not the pipe size.”